Pin type insulator ANSI 56 standard parameter of C29.6
Pin type insulator ANSI 56 consists of a single piece of ceramic or maybe two pieces of ceramic components permanently assembled together by cement. Porcelain pin type insulator is mounted rigidly on a supporting structure by an insulator pin or insulator spindle. Unless otherwise stated, this term does not include the insulator pin.
Creepage distance of pin type insulator ANSI 56: ANSI 56-1 is 330mm; ANSI 56-2 is 432mm; ANSI 56-3 is 533mm; ANSI 56-4 is 686mm; ANSI 56-5 is 865mm.
Power frequency dry flashover voltage of pin type insulator ANSI 56: ANSI 56-1 is 95KV; ANSI 56-2 is 110KV; ANSI 56-3 is 125KV; ANSI 56-4 is 140KV; ANSI 56-5 is 175KV.
Power frequency wet flashover voltage of pin type insulator ANSI 56: ANSI 56-1 is 60KV; ANSI 56-2 is 70KV; ANSI 56-3 is 80KV; ANSI 56-4 is 95KV; ANSI 56-5 is 125KV.
Radio influence test voltage to ground of pin type insulator ANSI 56: ANSI 56-1 is 15KV; ANSI 56-2 is 22KV; ANSI 56-3 is 30KV; ANSI 56-4 is 35KV; ANSI 56-5 is 44KV.
Dry arcing distance of pin type insulator ANSI 56: ANSI 56-1 is 178mm; ANSI 56-2 is 203mm; ANSI 56-3 is 229mm; ANSI 56-4 is 279mm; ANSI 56-5 is 356mm.
Each insulator, including ANSI 56-1, 56-2, 56-3, 56-4, 56-5 pin type insulator, shall bear a symbol identifying the insulator manufacturer. The marking shall be legible and durable.