ANSI 56-1,56-2,56-3,56-4,56-5 pin type insulator
Definition of ANSI 56-1, 56-2, 56-3, 56-4, 56-5 pin type insulator:
ANSI 56-1, 56-2, 56-3, 56-4, 56-5 pin type insulator consists of a single piece of ceramic or two or more ceramic components permanently connected together.
ANSI 56-1, 56-2, 56-3, 56-4, 56-5 pin type insulator ANSI 56 series pin type insulator
Referenced American National Standards:
ANSI C29.6-1996, American National Standard for Wet-Process Porcelain Insulators—High-Voltage Pin Type. This standard is intended for use in conjunction with the following American National Standards:
ANSI C29.1-1982, Test Methods for Electrical Power Insulators
ANSI Z55.1-1967(R1973), Gray Finishes for Industrial Apparatus and Equipment
Manufacturer’s drawing of ANSI 56-1, 56-2, 56-3, 56-4, 56-5 pin type insulator, if furnished, shall show the outline of the insulators, together with all pertinent dimensions. Any variations in these dimensions due to manufacturing tolerances shall be indicated.
Material of ANSI 56-1, 56-2, 56-3, 56-4, 56-5 pin type insulator:
ANSI 56-1, 56-2, 56-3, 56-4, 56-5 pin type insulator shall be made of good commercial-grade wet-process porcelain. The entire surface of the insulators, with the exception of a firing surface, shall be glazed. The entire surface shall be relatively free from imperfections. Color is not a part of this standard. Metal parts of ANSI 56-1, 56-2, 56-3, 56-4, 56-5 pin type insulator shall be made of a suitable corrosion resistance and temper.
Marking of pin insulator:
Each insulator, including ANSI 56-1, 56-2, 56-3, 56-4, 56-5 pin type insulator, shall bear a symbol identifying the manufacturer. The marking shall be legible and durable.
More insulator picture, electrical fitting or insulator test informations and so on, please contact us or enjoy visiting our website.
Type | 56-1 | 56-2 | 56-3 | 56-4 | 56-5 | ||
Main dimensions (mm) | H | 146 | 165 | 191 | 241 | 318 | |
h | 51 | 51 | 51 | 51 | 63.5 | ||
D | 191 | 228 | 267 | 305 | 343 | ||
d | 35 | 35 | 35 | 35 | 35 | ||
R1 | 19 | 19 | 19 | 19 | 19 | ||
R2 | 14 | 14 | 14 | 14 | 14 | ||
Creepage distance-mm | 330 | 432 | 533 | 686 | 865 | ||
Flashover voltage-kV | Power frequency | Dry | 95 | 110 | 125 | 140 | 175 |
Wet | 60 | 70 | 80 | 95 | 125 | ||
50% impulse | Pos. | 150 | 175 | 200 | 225 | 270 | |
Neg. | 190 | 225 | 265 | 310 | 340 | ||
Radio influence voltage | Test voltage to ground-KV | 15 | 22 | 30 | 30 | 44 | |
Max. RIV at 1000kHz-μv | 100 | 100 | 200 | 200 | 200 | ||
Low freq. Puncture voltage-kV | 130 | 145 | 165 | 185 | 225 | ||
Dry arcing distance-mm | 178 | 203 | 229 | 279 | 356 | ||
Cantilever failing load-lb/kN | 2500/11 | 3000/13 | 3000/13 | 3000/13 | 3000/13 |